PLANT SITING AND LAYOUT 59A?7
2001 Edition
important structures,equipment, or adjoining property or
that could reach waterways:
(1) Process areas
(2) Vaporization areas
(3) Transferareas for LNG, flammable refrigerants, and
flammable liquids
(4)Areas immediately surrounding flammable refrigerant
and flammable liquid storage tanksIf impounding areas also are required in order to complywith 2.1.2, such areas shall be in accordance with 2.2.2and 2.2.3.
2.2.1.3 In certain installations, the provisions of 2.1.2,2.2.1.1,
and 2.2.1.2 that apply to adjoining property or waterwaysshall
be permitted to be waived or altered at thediscretion of the
authority having jurisdiction where the change doesnot constitute
a distinct hazard to life or property orconflict with
applicable federal, state, and local (national, provincial,and
local) regulations.
2.2.1.4 Flammable liquid and flammable refrigerant storagetanks shall not be located within an LNG container impoundingarea.
2.2.2 Impounding Area and Drainage System Design and
Capacity.2.2.2.1 Impounding areas serving LNG containers shall have
a minimumvolumetric holding capacity, V, including any useful
holding capacity ofthe drainage area and with allowance
made for the displacementof snow accumulation, other containers,
and equipment, in accordance withthe following:
(1) For impounding areas serving a singlecontainer, V equals
the total volume of liquid in thecontainer, assuming the
container is full.
(2) For impoundingareas serving more than one container
with provision made toprevent low temperature or fire
exposure resulting from leakage fromany one container
served from causing subsequent leakage from anyother
container served, V equals the total volume of liquidin the
largest container served, assuming the container is full.(3) For impounding areas serving more than one containerwithout provision made in accordance with 2.2.2.1(b),
V equalsthe total volume of liquid in all containers
served, assumingall containers are full.
2.2.2.2 Impounding areas, if provided toserve only vaporization,
process, or LNG transfer areas, shall havea minimum volumetric
capacity equal to the greatest volume ofLNG,
flammable refrigerant, or flammable liquid that can be dischargedinto the area during a 10-minute period from anysingle
accidental leakage source or during a shorter time periodbased upon demonstrable surveillance and shutdown provisions
acceptable to theauthority having jurisdiction.
2.2.2.3 Enclosed drainage channels for LNG shallbe prohibited.
Exception: Container downcomers used to rapidly conduct spilledLNG away from critical areas shall be permitted to beenclosed if they
are sized for the anticipated liquid flowand vapor formation rates.
2.2.2.4 Dikes, impounding walls, and drainagesystems for
LNG and flammable refrigerant containment shall be ofcompacted
earth, concrete, metal, or other materials. They shall bepermitted to be independent of the container, or they shallbe
permitted to be mounded integral to, or constructed against,the container. They, and any penetrations thereof, shall be
designedto withstand the full hydrostatic head of impounded
LNG orflammable refrigerant, the effect of rapid cooling to
the temperatureof the liquid to be confined, any anticipated
fire exposure,and natural forces, such as earthquakes, wind,
and rain. Wherethe outer shell of a double-wall tank complies
withthese requirements, it shall be permitted to be considered
asthe impounding area for purposes of determining the siting
areadistances in 2.2.3. Where the containment integrity of
such anouter shell can be affected by an inner tank failuremode, an additional impounding area that otherwise satisfies
the requirementsof 2.2.1.1 shall be provided.
2.2.2.5 Dikes, impounding walls, anddrainage channels for
flammable liquid containment shall conform to NFPA30,
Flammable and Combustible Liquids Code.
2.2.2.6 The dike orimpounding wall height and distance
from containers operating at 15psi (100 kPa) or less shall be
determined inaccordance with Figure 2.2.2.6.
FIGURE 2.2.2.6 Dike or impoundment wallproximity to
containers.
2.2.2.7 Provision shall be made to clearrain or other water
from the impounding area. Automatically controlledsump
pumps shall be permitted if equipped with an automaticcutoff
device that prevents their operation when exposed to LNGtemperatures. Piping, valves, and fittings whose failure could
allow liquidto escape from the impounding area shall be capable
ofwithstanding continuous exposure to LNG temperatures.
If gravity drainage isemployed for water removal,
provision shall be made to preventthe escape of LNG by way
of the drainage system.2.2.2.8 Insulation systems used for impounding surfaces shall
be, inthe installed condition, noncombustible and suitable
for the intended service,considering the anticipated thermal
and mechanical stresses and loads. Ifflotation is a problem,
mitigating measures shall be provided.
2.2.3Impounding Area Siting.
2.2.3.1 The provisions of 2.2.3 shall notapply to impounding
areas serving only transfer areas at thewater? edge of marine
terminals.
Maximum liquid level
Container
XX
Y Y
Dike or impounding wall
Notes:
? DimensionX shall equal or exceed the sum of dimension Yplus the
equivalent head in LNG of the pressure inthe vapor space above
the liquid.
Exception: When the heightof the dike or impounding wall is equal to,
orgreater than, the maximum liquid level, X may have anyvalue.
? Dimension X is the distance from the innerwall of the container to the
closest face of thedike or impounding wall.
? Dimension Y is the distancefrom the maximum liquid level in the
container to thetop of the dike or impounding wall.