64 ANSI/ASHRAE/IESNA Standard 90.1-2007
Retail Area 4 = the floor area used for the sale of jewelry,
crystal, and china.
Exception: Other merchandise categories may be included in
Retail Areas 2 through 4 above, provided that justification
documenting the need for additional lighting power based
on visual inspection, contrast, or other critical display is
approved by the authority having jurisdiction.
9.7 Submittals (Not Used)
9.8 Product Information (Not Used)
10. OTHER EQUIPMENT
10.1 General
10.1.1 Scope. This section applies only to the equipment
described below.
10.1.1.1 New Buildings. Other equipment installed in
new buildings shall comply with the requirements of this section.
10.1.1.2 Additions to Existing Buildings. Other equipment
installed in additions to existing buildings shall comply
with the requirements of this section.
10.1.1.3 Alterations to Existing Buildings
10.1.1.3.1 Alterations to other building service equipment
or systems shall comply with the requirements of this
section applicable to those specific portions of the building
and its systems that are being altered.
10.1.1.3.2 Any new equipment subject to the requirements
of this section that is installed in conjunction with the
alterations, as a direct replacement of existing equipment or
control devices, shall comply with the specific requirements
applicable to that equipment or control devices.
Exception: Compliance shall not be required for the relocation
or reuse of existing equipment.
10.2 Compliance Path(s)
10.2.1 Compliance with Section 10 shall be achieved by
meeting all requirements of Section 10.1, General; Section 10.4,
Mandatory Provisions; and Section 10.8, Product Information.
10.2.2 Projects using the Energy Cost Budget Method
(Section 11 of this standard) must comply with Section 10.4,
the mandatory provisions of this section, as a portion of that
compliance path.
10.3 Simplified/Small Building Option (Not Used)
10.4 Mandatory Provisions
10.4.1 Electric Motors. Electric motors shall comply
with the requirements of the Energy Policy Act of 1992 where
applicable, as shown in Table 10.8. Motors that are not
included in the scope of the Energy Policy Act of 1992 have
no performance requirements in this section.
Common Space Typesa LPD, W/ft2 Building-Specific Space Types LPD, W/ft2
Workshop 1.9 Religious Buildings
Sales Area [for accent lighting, see Section 9.6.2(b)] 1.7 Worship Pulpit, Choir 2.4
Fellowship Hall 0.9
Retail
Sales Area [for accent lighting, see Section 9.6.3(c)] 1.7
Mall Concourse 1.7
Sports Arena
Ring Sports Area 2.7
Court Sports Area 2.3
Indoor Playing Field Area 1.4
Warehouse
Fine Material Storage 1.4
Medium/Bulky Material Storage 0.9
Parking Garage?arage Area 0.2
Transportation
Airport?oncourse 0.6
Air/Train/Bus?aggage Area 1.0
Terminal?icket Counter 1.5
a In cases where both a common space type and a building-specific type are listed, the building specific space type shall apply.
TABLE 9.6.1 Lighting Power Densities Using the Space-by-Space Method (continued)