Help
RealRead
48 ANSI/ASHRAE/IESNA Standard 90.1-2007 TABLE 6.8.1D Electrically Operated Packaged Terminal Air Conditioners, Packaged Terminal Heat Pumps, Single-Package Vertical Air Conditioners, Single-Package Vertical Heat Pumps, Room Air Conditioners, and Room Air-Conditioner Heat Pumps?inimum Efficiency Requirements Equipment Type Size Category (Input) Subcategory or Rating Condition Minimum Efficiency Test Procedurea PTAC (cooling mode) new construction All capacities 95?F db outdoor air 12.5 ? (0.213 ? Cap/1000)c EER ARI 310/380 PTAC (cooling mode) replacementsb All capacities 95?F db outdoor air 10.9 ? (0.213 ? Cap/1000)c EER PTHP (cooling mode) new construction All capacities 95?F db outdoor air 12.3 ? (0.213 ? Cap/1000)c EER PTHP (cooling mode) replacementsb All capacities 95?F db outdoor air 10.8 ? (0.213 ? Cap/1000)c EER PTHP (heating mode) new construction All capacities 3.2 ? (0.026 ? Cap/1000)c COP PTHP (heating mode) replacementsb All capacities 2.9 ? (0.026 ? Cap/1000)c COP SPVAC (cooling mode) <65,000 Btu/h 95?F db/75?F wb outdoor air 9.0 EER ARI 390 .65,000 Btu/h and <135,000 Btu/h 95?F db/75?F wb outdoor air 8.9EER .135,000 Btu/h and <240,000 Btu/h 95?F db/75?F wb outdoor air 8.6 EER SPVHP (cooling mode) <65,000 Btu/h 95?F db/75?F wb outdoor air 9.0. EER .65,000 Btu/h and <135,000 Btu/h 95?F db/75?F wb outdoor air 8.9 EER .135,000 Btu/h and <240,000 Btu/h 95?F db/75?F wb outdoor air 8.6 EER SPVHP (heating mode) <65,000 Btu/h 47?F db/43?F wb outdoor air 3.0 COP .65,000 Btu/h and <135,000 Btu/h 47?F db/43?F wb outdoor air 3.0 COP .135,000 Btu/h and <240,000 Btu/h 47?F db/43?F wb outdoor air 2.9 COP