48 ANSI/ASHRAE/IESNA Standard 90.1-2007
TABLE 6.8.1D Electrically Operated Packaged Terminal Air Conditioners, Packaged Terminal Heat Pumps,
Single-Package Vertical Air Conditioners, Single-Package Vertical Heat Pumps,
Room Air Conditioners, and Room Air-Conditioner Heat Pumps?inimum Efficiency Requirements
Equipment Type Size Category (Input) Subcategory or
Rating Condition Minimum Efficiency Test
Procedurea
PTAC (cooling mode)
new construction All capacities 95?F db outdoor air 12.5 ? (0.213 ?
Cap/1000)c EER
ARI 310/380
PTAC (cooling mode)
replacementsb All capacities 95?F db outdoor air 10.9 ? (0.213 ?
Cap/1000)c EER
PTHP (cooling mode)
new construction All capacities 95?F db outdoor air 12.3 ? (0.213 ?
Cap/1000)c EER
PTHP (cooling mode)
replacementsb All capacities 95?F db outdoor air 10.8 ? (0.213 ?
Cap/1000)c EER
PTHP (heating mode)
new construction All capacities 3.2 ? (0.026 ?
Cap/1000)c COP
PTHP (heating mode)
replacementsb All capacities 2.9 ? (0.026 ?
Cap/1000)c COP
SPVAC (cooling mode)
<65,000 Btu/h 95?F db/75?F wb outdoor air 9.0 EER
ARI 390
.65,000 Btu/h and
<135,000 Btu/h 95?F db/75?F wb outdoor air 8.9EER
.135,000 Btu/h and
<240,000 Btu/h 95?F db/75?F wb outdoor air 8.6 EER
SPVHP (cooling mode)
<65,000 Btu/h 95?F db/75?F wb outdoor air 9.0. EER
.65,000 Btu/h and
<135,000 Btu/h 95?F db/75?F wb outdoor air 8.9 EER
.135,000 Btu/h and
<240,000 Btu/h 95?F db/75?F wb outdoor air 8.6 EER
SPVHP (heating mode)
<65,000 Btu/h 47?F db/43?F wb outdoor air 3.0 COP
.65,000 Btu/h and
<135,000 Btu/h 47?F db/43?F wb outdoor air 3.0 COP
.135,000 Btu/h and
<240,000 Btu/h 47?F db/43?F wb outdoor air 2.9 COP