ANSI/ASHRAE/IESNA Standard 90.1-2007 47
TABLE 6.8.1C Water Chilling Packages?inimum Efficiency Requirements
Equipment Type Size Category Subcategory or
Rating Condition Minimum Efficiencya Test
Procedureb
Air cooled, with condenser,
electrically operated All capacities ? 2.80 COP
3.05 IPLV
Air cooled, ARI 550/590
without condenser,
electrically operated
All capacities ? 3.10 COP
3.45 IPLV
Water cooled, electrically
operated, positive displacement
(reciprocating)
All capacities ? 4.20 COP
5.05 IPLV ARI 550/590
Water cooled,
electrically operated,
positive displacement
(rotary screw and scroll)
<150 tons ? 4.45 COP
5.20 IPLV
ARI 550/590 .150 tons and
<300 tons ? 4.90 COP
5.60 IPLV
.300 tons ? 5.50 COP
6.15 IPLV
Water cooled, electrically
operated, centrifugal
<150 tons ? 5.00 COP
5.25 IPLV
. ARI 550/590 150 tons and
<300 tons ? 5.55 COP
5.90 IPLV
.300 tons ? 6.10 COP
6.40 IPLV
Air-cooled absorption
single effect All capacities ? 0.60 COP
ARI 560
Water-cooled absorption
single effect All capacities ? 0.70 COP
Absorption double effect,
indirect-fired All capacities ? 1.00 COP
1.05 IPLV
Absorption double effect,
direct-fired All capacities ? 1.00 COP
1.00 IPLV
a The chiller equipment requirements do not apply for chillers used in low-temperature applications where the design leaving fluid temperature is <40?F.
b Section 12 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure.